Dimension range | PN | Temperature range | Material |
---|---|---|---|
G 1/2 | 16 | 0 - 180 °C | Stainless steel, Brass |
1 | Resistor element | Platinum Pt 500 |
2 | Protection sleeve | Stainless steel |
3 | Gland | brass |
4 | Connection cable | silicone |
5 | Thermowell | Stainless steel, nickel-plated brass or brass |
Fig No | AT 7276-150PT500 | AT 7276-100PT500 | AT 7276-45PT500 | ||||||
---|---|---|---|---|---|---|---|---|---|
AT 7279-150 | AT 7279-100 | AT 7279-45 | AT 7279-85 | AT 7279-120 | AT 7279-155 | ||||
A | 150 | 100 | 45 | 85 | 120 | 155 | |||
B | 150 | 100 | 45 | ||||||
C | G 1/2 | G 1/2 | G 1/2 | G 1/2 | G 1/2 | G 1/2 | |||
D | 6 | 6 | 5,2 | 5,2 | 5,2 | 5,2 | |||
E | G 1/4 | G 1/4 | - | - | - | - | |||
Dimensions in mm |
The temperature sensors are in Pt 500 performance, i.e. resistance 500 Ohm at 0oC. Different temperatures gives different resistance figures. Pt 500 has a higher resolution on the temperature and a lower energy consumption than, for example, the Pt 100 sensor at e.g. battery operation for connected measuring equipment.
The temperature sensors are also approved for use without thermowells. The sensors are delivered in pairs, with 2 m 2*0,35 mm2 shielded cable. The screen is intended to protect against the over inductance from the outside.
Sensor type: | Pt 500 acc. to DIN 43760 |
Temperature range: | 0-180 °C |
Dykrör | |
AT 7279-45 | Thermowell of brass, G 1/2 utv., plug 45 mm |
AT 7279-85 | Thermowell of brass, G 1/2 utv., plug 85 mm |
AT 7279-120 | Thermowell of Stainless steel, G 1/2 utv., plug 120 mm. |
AT 7279-155 | Thermowell of Stainless steel, G 1/2 utv., plug 155 mm. |
for AT 7500F | |
AT 7279-100 | Thermowell of Stainless steel, G 1/2 utv., plug 100 mm. |
AT 7279-150 | Thermowell of Stainless steel, G 1/2 utv., plug 150 mm. |
The temperature sensors are mounted with thermowells in flow pipes acc. to illustration.
When extending the cables use multilayer signal cable 2*0.75 mm2 (proposedly LiYCY). It is important that the total length of the two cables is equal. However, you should not extend more than one to one acc. to below:
Example: AT 7276-45PT500 | ||
---|---|---|
AT 7276 | -45 | PT500 |
Fig. nr. | Insertion lenght mm. | Option Pt 500-sensor |
Quantity given in pairs | -27 | |
-45 | ||
AT 7279=Thermowell | -45 | |
-85 |