Electric actuator for on/off or positioning of ball valves, butterfly or where a 90° rotation is needed.
Torque | 45 Nm to 150 Nm |
---|---|
Drive | Electric |
Fits valves: | AT3502, AT3507, AT3533S, AT3534S, AT3542, AT3547, AT3582, AT3585, AT3590, AT2282, AT 2310-2319, AT2270B |
Article number | Amount |
---|---|
AT 3900-4-3A3A | |
AT 3900-6-3A3A | |
AT 3900-6-3A0A | |
AT 3900-6-3A4A | |
AT 3900-10-3A3A | |
AT 3900-10-9A3C | |
AT 3900-10-9A0A | |
AT 3900-10-9A0C | |
AT 3900-10-3A4A | |
AT 3900-10-9A4C | |
AT 3900-15-7A3A | |
AT 3900-15-7A3C | |
AT 3900-15-7A0A | |
AT 3900-15-7A0C | |
AT 3900-15-7A4A | |
AT 3900-15-7A4C |
UEC.11 Actuator for valve, electric, two-position without spring return
Actuator Bernard Electrical AT 3900 for 90°. Maneuvering of ball valves, butterfly or where a 90° rotation is needed.
CE-Marking
EC Directives 2004/108/EC, 2006 /95/EC and fulfills the EN 61000-6-4, EN 61000-6-2, EN 60034-1 and EN 60529.
IP 67 rated.
Detail | Material | Surface treatment | |
---|---|---|---|
1 | Body | Aluminum | Epoxy painted RAL 2010 |
2 | Cover | Aluminum | Epoxy painted RAL 2010 |
3 | Drive shaft | Massive steel | Untreated |
Actuator/Fig. no | Standard drive | A | B | C | Weight | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
3900-4 | 14* | 273 | 200 | 225 | 6 | |||||||||||||||||
3900-6 | 14* | 319 | 200 | 225 | 7 | |||||||||||||||||
3900-10 | 19* | 362 | 200 | 225 | 7 | |||||||||||||||||
3900-15 | 19* | 362 | 200 | 225 | 7 | |||||||||||||||||
Dimension in mm, weight in kg. *Possible to get in different sizes. |
Standard version
Reversible actuator in four sizes, for 0-90° rotation, adjustable through a combination of cams, mechanical end stop and/or torque switch.
The acutator is a compact combination of an electric motor with thermal overload protection and self-locking, permanently lubricated worm gear. Standard with manual emergency operation and position indicator.
The actuator mounting-dimensions in relation to the fittings are according to ISO 5211.
Design lifetime 20 000 cycles for on/off or 300 000 starts for positioning. Tested according to EN 15714-2 class A and B
Standard performance | ||||
Motor duty | S4-25% ED. 360 starts/h max | |||
Enclosures | IP67 | |||
Temperature | -20°C to +60°C | |||
Anti condensation heater | Yes | |||
Overload protection | Thermostats | |||
Permanently lubricated gear | Yes | |||
Cable entries | 2 pcs.M20x1,5 for On/Off, 3 pcs for reglulating | |||
End position switches | 250V, max 16A | |||
Torque | - | |||
Terminal block | 8 connections | |||
Actuator 3900 on/off | Torque Nm | Operating time s/90 | ISO-Connection | 230 V AC 50 Hz Ampere | 400 V AC 50 Hz Ampere | 24 V DC | |||||
---|---|---|---|---|---|---|---|---|---|---|---|
Start | Stop | Start | Stop | Kw | Start | Stop | Kw | Operating time | |||
4 | 45 | 45 | 6 | F05/07 | 0,5 | 0,4 | 0,02 | - | - | - | - |
6 | 60 | 60 | 6 | F05/07 | 0,9 | 0,6 | 0,03 | 0,5 | 0,3 | 0,03 | 6 |
10 | 100 | 100 | 6 | F05/07 | 1,7 | 1,2 | 0,06 | 1,1 | 0,6 | 0,10 | - |
10 | 100 | 100 | 35 | F05/07 | 0,9 | 0,6 | 0,03 | 0,5 | 0,3 | 0,03 | 35 |
15 | 150 | 150 | 25 | F05/07 | 0,9 | 0,6 | 0,03 | 0,5 | 0,3 | 0,03 | 15 |
Actuator 3900 for positioning | Torque Nm | Operating time (50 Hz) s | ISO-connection | 230 V AC 50 Hz Ampere | |||
---|---|---|---|---|---|---|---|
Start | Stop | Start | Stop | Kw | |||
10 | 100 | 50 | 35 | F05/07 | 0,6 | 0,5 | 0,02 |
15 | 150 | 75 | 25 | F05/07 | 0,9 | 0,6 | 0,03 |
Acutator | 3900-4 | 3900-6 | 3900-10 | 3900-15 | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Valve type | D p, bar | |||||||||||||||
Ball valve 3 piece | 25 | DN | 8-40 | 50 | 65 | 80 | ||||||||||
AT3502-3552 | ||||||||||||||||
Ball valve flanged | 16 | DN | 15-40 | 50 | 65-80 | 100 | ||||||||||
AT3580-3585 | ||||||||||||||||
Butterfly valve | 10 | DN | 50-100 | 125 | 150 | |||||||||||
AT2310-2319 | ||||||||||||||||
Butterfly valve | 10 | DN | 32-80 | 100 | 125 | |||||||||||
On/off is avaliable in two different variants
1. The basic version with electromechanical circuit breaker. A feedback signal (4-20mA) is possible with accessories POT and TAM.
2. With LCD display and push buttons, this includes control with either 4-20 mA or 0-10 V.
For regulatory
During all work with the actuator, the power MUST be disconnected.
- The actuator must be connected as per the wiring diagram, see the manual.
- Each actuator must be powered by an individual switch or relay contact, minimum 16A, to prevent cross-feed between the actuators.
- At outdoor installation, the actuator should be protected by a roof or cap.
- Installation with the motor downwards should be avoided.
- Turn the valve with the control unit's hand wheel to centre position. See indication on top of the device.
- Always connect the heater.
- Check that the actuator turns the valve in the desired direction.
- The correct limit switch (open or closed) shall break the motor current.
- Cable entries must comply at least to the lowest protection class of devices.
See the manual for start-up, storage and maintenance.
Article number, manufacturer, serial number, voltage and current.
Wiring diagram is placed by the motor at delivery.
Example: 3900-4-3A3A | |||||
AT3900 | -4* | 3** | A*** | 3**** | A***** |
Fig. no. | Size | Operating time | Connection | Voltage | Options |
Example: 3900-4-3A3C (Positioning qith 4-20mA or 0-10V signal) | |||||
* 4, 6, 10 or 15 depending on needed torque | |||||
** 3=6 s, 7=25 s, 9=35s, see Technical data for possible time | |||||
*** A=F05/07 | |||||
**** 0=24 VDC, 3=230 VAC, 4=3-phase 400 VAC (Size 4 is not available as 400 VAC or 24 VDC) | |||||
***** A=On/Off, B= On/off Logic, C=Positioning D=, E=1000 ohm POT, I=TAM |